The FCXtreme Series provides reliable solid-state converters that are designed to provide 400Hz ground power with a small footprint in applications such as inside aircraft hangars, in electrical equipment rooms, or in maintenance shops.
- Individual phase regulation, improved efficiency, and lower
input current distortion - Innovative, adaptive wave optimization and voltage
stabilization - Laminated bus design eliminates transient voltage surges for
high performance and increased reliability - Lightweight powder-coated steel enclosure with sealed
electronics compartment superior to typical aluminum
enclosures to reduce RF emissions - Full-featured user interface with detailed troubleshooting
menus added to the advanced diagnostic and logging system - High contrast LED display with 16-button keypad and separate
standalone controls to ensure ease of use for most frequent
functions - Standard RS485 Modbus communication and integration
capability with available RJ45 Ethernet and Wi-Fi connection
capability
60kva /60kw continuous, 90kva / 90kw continuous, 180kva / 180kw continuous
-
INPUT POWER
Input Voltage 380-415V, 3ph, 50Hz / 480V, 3ph, 60Hz ± 10% (Other voltages available upon request) Input Power Factor 0.8 to Unity (1.0) (Typically ≥0.95 at 50% and above) Surge Protection Integral Surge Supression compliant with UL 1449 and IEEE C62.41.1 and IEEE C62.41.1 (Location Category B) requirements Inrush Current None, Soft Charge to rated voltage Input Current Distortion <5% at full rated load -
INPUT AND OUTPUT CONNECTIONS
Circuit Breaker Circuit breaker conforming to UL489 Input Circuit Breaker UL listed thermal magnetic trip circuit breaker Output Contactor Three pole, magnetic coil contactor rated for full load, overload, and short circuit conditions. Contactor internlocked with all protective controls to open in the event of fault condition. (Typical for aircraft cable applications) Output Circuit Breaker UL listed molded case switch derated for 400Hz application. (Typcial for distribution applications) Aircraft Interlock Circuit A safety interlock circuit included on the unit output to detect 28VDC feedback signal from the aircraft. Bypass function supplied as well -
OUTPUT POWER
Output Voltage 200/115V, 3ph, 400Hz or 208/120V, 3ph, 400Hz (Other votlages available upon request) Power Output 60kVA/60kW continuous, 75kVA/75 kW continuous, 90kVA/90 kW continuous, 120kVA/120 kW continuous, 140kVA/140 kW continuous, 160kVA/160 kW continuous, 180kVA/180 kW continuous Efficiency ≥ 87% @ 50% Load ≥91% @ 100% Load (Note: Systems requiring an input transformer, apply 2% reduction to efficiency numbers) No Load input Losses ≤7% of converter output kW rating (Typically ≤5%) Overload 110% (60 minutes), 125% (5 minutes), 150% (2 minutes), 200% (20 seconds) Standard. 300% (4 seconds) Optional Short Circuit System designed and tested to withstand short circuit current (bolted line to ground fault and bolted three phase fault) without damage until the integral protective controls and devices interrupt the fault Output Voltage THD ≤3% L-L / L-N for Linear Loads, ≤5% L-L / L-N for Non-Linear Loads, ≤4% for Unbalanced (15%) Linear Loads Output Voltage Amplitude Modulation ≤0.5% of nominal votlage rating, no load to full load Frequency Stability ±0.01% under all operating conditions Phase Angle Regulation 120° between adjacent phases ±2° (Balanced Load), 120° between adjacent phases ±4° (15% Unbalanced Load) Transient Output Voltage Recovery Meets or exceeds MIL-STD-704F -
PROTECTION
Input Under/Over Voltage, Phase Loss, Input Power Loss, Access Door(s) Interlock, Output Under/Over Voltage per Mil-STD-704F, Output Overload, and Over Temperature -
AUTOMATIC LINE DROP COMPENSATION
Adjustable automatic line drop compensation, configurable from 0 - 10% -
ACOUSTICAL NOISE
Less than 72dbA typical @ 1m -
ASSEMBLY CONSTRUCTION
Enclosure is suitable for indoor or outdoor environments and provides protection equivalent to NEMA 250, Type 3R. Integral forced air cooling intake and exhaust openings are covered as required. All components except for the user interface are totally enclosed within the enclsoure. Design employs modular construction for ease of maintenance and repair. All wiring uniquely indentified with indentification throughly documented in as built schematics provided with Operation & Maintenance manual. Finish is durable, scratch resistant, rust inhibiting, electrostatically applied powder coat finish. Standard color: White Aluminum (RAL 9006). Other colors available upon request. -
CODES AND STANDARDS
Meets or Exceeds UFGS 26 35 43 SAE ARP-5015 NFPA 70 BS2G-219 UL 1012 DFS-400 MIL-STD-704F -
ENVIRONMENTAL RATING
Ambient Temp. Range Operating: -40˚C to +55˚C (-40˚F to +131˚F)) Relative Humidity Range 10 to 95% w/out condensation Ambient Pressure Sea Level to 9843ft (3000m) -
MONITORING AND CONTROLS PANEL
Controls Start, Stop/Reset, Output On/Off, Emergency Stop Indicators LED indicators: Power On, Converter On, Module Fault, Input Voltage Fault, Output Voltage Fault, Overload, 28VDC E/F Interlock, 28VDC E/F Bypass Mode, Output 1 On, Output 2 On Instrumentation 4 Line by 20 Character Backlit Display Data Logging Total of 200 events (100 Events per unit when dual outputs are incorporated) Diagnostics System designed with built-in test circuit that monitors both primary and protective circuits of the unit. Performs system check of each circuit board and communication port to internal component interfaces. Alarm Functions Audible Alarm rated 80dB(A) @ 2ft w/ Alarm silence function & indicator activates when system fault condition is detected -
OPTION AND ACCESSORIES
28.5VDC Output with 600A rating Integral single cable rack Freestanding or wall mount cable racks Output circuit breaker for distributed power applications Dual or Triple output contactors Remote operators station(s) Output power cables Power usage monitoring 300% overload for 60/90kVA units Split F interlock MV/CV-22 interlock -
Suitable For:
Fixed and Rotary Wing Aircraft and All Other 400 Hz Applications -
CODES AND STANDARDS
UFGS 26 35 43MIL-STD-704FBS2G-219NFPA 70SAE ARP-5015DFS-400 -
OPTIONS AND ACCESSORIES
28.5VDC Output with 600A ratingDual outputs Integral single cable rackFreestanding or wall mount cable racksOutput circuit breaker for distributed power applicationsDual or Triple output contactorsWi-Fi communications integrationFloor stand kitRemote operators station(s)Output power cablesPower usage monitoring300% overload for 60/90 kVA units