The FCXtreme Series provides reliable solid-state converters that are designed to provide 400Hz ground power with a small footprint in applications such as inside aircraft hangars, in electrical equipment rooms, or in maintenance shops.
- Individual phase regulation, improved efficiency, and lower
input current distortion - Innovative, adaptive wave optimization and voltage
stabilization - Laminated bus design eliminates transient voltage surges for
high performance and increased reliability - Lightweight powder-coated steel enclosure with sealed
electronics compartment superior to typical aluminum
enclosures to reduce RF emissions - Full-featured user interface with detailed troubleshooting
menus added to the advanced diagnostic and logging system - High contrast LED display with 16-button keypad and separate
standalone controls to ensure ease of use for most frequent
functions - Standard RS485 Modbus communication and integration
capability with available RJ45 Ethernet and Wi-Fi connection
capability

60kva /60kw continuous, 90kva / 90kw continuous, 180kva / 180kw continuous
-
UNIT PERFORMANCE
Efficiency 93% or better at 100% load 28VDC Output Available 600A rated 28VDC output with 400% surge rating MTTR Mean time to repair: less than 30 minutes Operational Life 20 to 25 years MTBF Mean time between failure: 24,000 hours -
INPUT POWER
Input Voltage 480VAC +/- 10% standard, other input voltages available Input Frequency 60Hz +/- 1Hz standard, 50Hz optional Input Phase Rotation Any (automatic phase lock) Inrush Current None (soft start to rated power) Protection Overload, short circuit, over voltage, temperature, access door interlock Input ITHD <5% at rated load, <8% at any load -
OUTPUT POWER
Output Power Rating 60kVA/60kW continuous, 90kVA/90kW continuous, 120kVA/120kW continuous, 180kVA/180kW continuous Output Frequency 400Hz, +/- 0.01% for any load condition Output Voltage 200V L-L / 115V L-N – adjustable +/- 10% Voltage Regulation +/- 1% Maximum Voltage Recovery Meets or exceeds limits of MIL-STD-704F, typically less than 50 milliseconds with a 100% load change Voltage Balance +/- 1% for balanced loads, +/- 2% for 25% unbalanced loads Harmonic Content 1.5% max., 1% typical (line to line or line to neutral) Overload Capacity 125% for one hour, 150% for 5 minutes, 200% for 20 seconds Protection Overload, short circuit, over and under voltage per MIL-STD-704F, over temperature, isolation, aircraft 28VDC E/F interlock, access door interlock -
MONITORING AND CONTROLS
Display 4 x 20 character backlit display and dedicated indicator lights, with LED configuration for harsh environments Control 16-key matrix keypad for full control and monitoring, as well as dedicated stand alone push button controls for Start, Stop/Reset, and Output On/Off control for user friendly operation Metering Full three-phase monitoring and display of input and output voltage, current, and frequency; built-in troubleshooting guide in display; dedicated elapsed time meter also provided -
ENVIRONMENTAL
Enclosure NEMA 4 equivalent (IP66) Audible Noise Level Less than 65dbA typical @ 1m Ambient Temp. Range Operating: -40˚C to +50˚C (-40˚F to +122˚F) Humidity 0% to 100% without condensation Altitude 0 to 3,000 meters (9,842 ft.) without derating -
MECHANICAL
Construction Lightweight powder coated steel enclosure over durable steel frame with sealed electronics compartment Size 1981mm high x 1270mm wide x 706mm deep (78” x 50” x 27.8”) Weight 60-90 Series: 743 kg (1,640 lbs.) 120-180 Series: 997 kg (2,200 lbs.) Finish Standard color: “white aluminum” (gray) (RAL 9006) powder coat, other colors available -
Suitable For:
Fixed and Rotary Wing Aircraft and All Other 400 Hz Applications -
CODES AND STANDARDS
UFGS 26 35 43MIL-STD-704FBS2G-219NFPA 70SAE ARP-5015DFS-400 -
OPTIONS AND ACCESSORIES
28.5VDC Output with 600A ratingDual outputs Integral single cable rackFreestanding or wall mount cable racksOutput circuit breaker for distributed power applicationsDual or Triple output contactorsWi-Fi communications integrationFloor stand kitRemote operators station(s)Output power cablesPower usage monitoring300% overload for 60/90 kVA units